Sign Up

I've found a bug that prohibits re-connections if the connection to the PLC is lost. The PDU size will be set to 0 if no PLC is available. In a later connection request the PDU size of 0 will be requested during the communication setup. The PLC will close the TCP connection with an error 66 and no connection can't be established anymore.

Comments

Hampel Software Engineering Thanks for taking the time to report this back, Martin. We've created issue #33 in the repo at https://code.hampel-soft.com/open-source/s7netcom/-/issues/33 and will look into this ASAP.
 •  Reply6 months
Hampel Software Engineering Issue #33 has been fixed in v2.0.0 released just earlier today.
 •  Reply6 months

Please sign in to leave a comment.